Effect of operation conditions on the second law analysis of a desiccant cooling system

Yükleniyor...
Küçük Resim

Tarih

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Pergamon-Elsevier Science Ltd

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

In order to evaluate the potential of a desiccant based evaporative air conditioning system, a second law analysis of the systems was investigated. In this work, a wide range of working parameters that are regeneration temperature from 90 degrees C to 110 degrees C, volume flow rate from 2000 m(3) to 4000 m(3) and ambient air conditions which are relative humidity, ambient air temperature and wet-bulb temperature is carried out for performance calculation of the system. It is observed from results that the Carnot COP and the thermal COP of the system varies vice versa during the day. The highest value of Camot COP and the thermal COP is about 25 and 0.62, respectively. Also, the cooling capacity has significant effect on the second law efficiency. The importance of this study shows that the second law analysis can provide useful information with respect to the theoretical upper limit of the system performance, which cannot be obtained from the first law of thermodynamic analysis alone. (C) 2016 Elsevier Ltd. All rights reserved.

Açıklama

Anahtar Kelimeler

Air conditioning, Desiccant cooling system, Carnot COP, Second law analysis, Experimental data, Adsorption

Kaynak

Applied Thermal Engineering

WoS Q Değeri

Scopus Q Değeri

Cilt

113

Sayı

Künye

Onay

İnceleme

Ekleyen

Referans Veren