Thermal Performance Investigation of Vapor Chamber Under Partial Heating and Different Heat Flux Conditions: Effects of Inclination Angle

Yükleniyor...
Küçük Resim

Tarih

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Asme

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

The need for cooling technologies increases tremendously with raising demand on the powerful and compact electronics. There, it pushes the research and technology to the new investigations on varying heat transfer mechanisms and devices. While one of these devices is vapor chamber (VC), an experimental study has been carried out to investigate the heat transfer performance of a VC under partial heating, varying heat fluxes, and different inclination angles for different temperatures, in the current study. For this purpose, a VC with a dimension of 90 mm x 90 mm x 3 mm is evaluated via its resulting thermal resistance, performance, and the temperature distribution over the VC surface. There, the limited effect of inclination angle is observed on the performance, while the highest change is obtained with decreasing local heating surface area, thus increasing heat fluxes. Moreover, this trend is seen almost similar with a reasonable shift up or down according to the different temperature differences.

Açıklama

Anahtar Kelimeler

vapor chamber, heat transfer, partial heating and cooling, thermal performance, inclination angle

Kaynak

Asme Journal of Heat and Mass Transfer

WoS Q Değeri

Scopus Q Değeri

Cilt

147

Sayı

1

Künye

Onay

İnceleme

Ekleyen

Referans Veren