The experimental investigation of heat transfer and pressure drop in a tube with coiled wire inserts placed separately from the tube wall

dc.contributor.authorGunes, Sibel
dc.contributor.authorOzceyhan, Veysel
dc.contributor.authorBuyukalaca, Orhan
dc.date.accessioned2025-08-12T08:26:58Z
dc.date.issued2010
dc.departmentOsmaniye Korkut Ata Üniversitesi
dc.description.abstractThe paper presents the experimental investigation of heat transfer and pressure drop in a tube with coiled wire inserts placed separately from the tube wall in turbulent flow regime. The experiments were performed with a constant wire thickness of a = 6 mm, three different pitch ratios (P/D = 1, P/D = 2 and P/D = 3) and two different distances (s = 1 mm, s = 2 mm) at which the coiled wire inserts were placed separately from the tube wall. Uniform heat flux was applied to the external surface of the tube and Reynolds numbers varied from 4105 to 26 400 in the experiments. The experimental results obtained from a smooth tube were compared with those from the studies in literature for validation of experimental set up. The use of coiled wire inserts leads to a considerable increase in heat transfer and pressure drop over the smooth tube. The Nusselt number and friction factor increase with decreasing pitch ratio (P/D) and distance (s) for coiled wire inserts. The highest overall enhancement efficiency of 50% was achieved for the coiled wire with P/D = 1 and s = 1 mm at Reynolds number of 4220. As a result, the experimental results reveal that using these coiled wire inserts are thermodynamically advantageous at all Reynolds numbers. (C) 2010 Elsevier Ltd. All rights reserved.
dc.description.sponsorshipErciyes University [FBA-08-453, FBA-08-454, FBA-08-457]
dc.description.sponsorshipAuthors would like to acknowledge for the financial support of the Scientific Research Project Division of Erciyes University under the contract: FBA-08-453, FBA-08-454 and FBA-08-457.
dc.identifier.doi10.1016/j.applthermaleng.2010.04.001
dc.identifier.endpage1725
dc.identifier.issn1359-4311
dc.identifier.issn1873-5606
dc.identifier.issue13
dc.identifier.scopus2-s2.0-77955269301
dc.identifier.scopusqualityQ1
dc.identifier.startpage1719
dc.identifier.urihttps://doi.org/10.1016/j.applthermaleng.2010.04.001
dc.identifier.urihttps://hdl.handle.net/20.500.12502/5242
dc.identifier.volume30
dc.identifier.wosWOS:000279907800026
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherPergamon-Elsevier Science Ltd
dc.relation.ispartofApplied Thermal Engineering
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzKA_WOS_20250812
dc.subjectCoiled wire insert
dc.subjectHeat transfer
dc.subjectPressure drop
dc.subjectOverall enhancement efficiency
dc.titleThe experimental investigation of heat transfer and pressure drop in a tube with coiled wire inserts placed separately from the tube wall