Thermodynamic analysis of a refrigeration system with double evaporators and ejector
Yükleniyor...
Dosyalar
Tarih
Yazarlar
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
GAZI UNIV,
Erişim Hakkı
info:eu-repo/semantics/openAccess
Özet
In this study, theoretical investigations of double evaporator refrigeration system and with adding an ejector to the current system were carried out using energy and momentum equations. The relative increase in COP with respect to the conventional double evaporator refrigeration system was analyzed in terms of condenser and evaporator temperatures. Also exergy analyses of systems were examined and results were showed graphically. In the study, R134a and its potential substitute R1234yf were used. The analyses showed that COP improvements of the proposed system by using ejector as an expansion device were approximately 15% for R134a and about 17% for R1234yf, respectively.
Açıklama
Anahtar Kelimeler
Ejector, Double evaporator, Cooling effect, R1234yf, Exergy analysis
Kaynak
Journal of Faculty of Engineering And Architecture Of Gazi University
WoS Q Değeri
Scopus Q Değeri
Cilt
31
Sayı
4
Künye
Unal, S., Erdinc, M. T., Kutlu, C., (2016). Thermodynamic analysis of a refrigeration system with double evaporators and ejector. Journal of Faculty of Engineering And Architecture Of Gazi University. 31(4), 1039-1047. DOI: 10.17341/gazimmfd.278459